Chicago Department of Public Health reports Pass for GROVER CLEVELAND ELEMENTARY SCHOOL on .
Checked · Source updated
Most recent visit in the dataset
Latest inspection
Inspection date
Reported outcome
Pass
Inspection type
Canvass
Recorded citations
2
Source risk category
Risk 1 (High)
Inspection ID
2629559
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
Recorded violations
51
PLUMBING INSTALLED; PROPER BACKFLOW DEVICES - Comments: OBSERVED LEAKING FAUCET BASE AT THE 3-COMPARTMENT SINK LOCATED IN REAR MAIN KITCHEN AREA. MUST REPAIR LEAKING AND MAINTAINED.
55
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN - Comments: OBSERVED DUST BUILD UP INSIDE CEILING LIGHTSHIELD COVERS ON LUNCHROOM. MUST CLEAN AND MAINTAIN.
Official inspection record
Inspection history
Chicago publishes inspection reports dating back to 2010. The city changed its procedures on July 1, 2018.
Canvass Re-InspectionPass
Inspection date
Reported outcome
Pass
Inspection type
Canvass Re-Inspection
Recorded citations
1
Source risk category
Risk 1 (High)
Inspection ID
1603206
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
This visit predates Chicago’s July 1, 2018 inspection procedure change.
Recorded violations
35
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS - Comments: MUST REMOVE PEELING PAINT AT THE CEILING ON THE 3RD FLOOR ACROSS FROM ROOM 308.
CanvassPass with Conditions
Inspection date
Reported outcome
Pass with Conditions
Inspection type
Canvass
Recorded citations
3
Source risk category
Risk 1 (High)
Inspection ID
1631250
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
The source labels this outcome “Pass w/ Conditions”.
This visit predates Chicago’s July 1, 2018 inspection procedure change.
Recorded violations
2
FACILITIES TO MAINTAIN PROPER TEMPERATURE - Comments: DURING INSPECTION FOUND THE WALK-IN COOLER WITH AN OUT OF ORDER SIGN ON IT AND NO FOOD INSIDE UNIT. FACILITY HAS OTHER REFRIGERATION ON PREMISES IN ORDER TO SUSTAIN POTENTIALLY HAZARDOUS FOODS AT 40F AND BELOW (THERE ARE 2 ADDITIONAL LARGE REACH-IN REFRIGERATORS ON PREMISES IN WORKING ORDER).UNIT WAS TAGGED. DO NOT REMOVE TAG UNTIL CDPH INSPECTS UNIT. NO CITATION ISSUED.
35
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS - Comments: MUST REMOVE PEELING PAINT AT THE CEILING ON THE 3RD FLOOR ACROSS FROM ROOM 308.
38
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED - Comments: MUST TIGHTEN HOT WATER FAUCET HANDLE AT THE 3-COMP SINK ON THE MOST LEFT HAND SIDE TO PREVENT LEAK AT BASE.
CanvassPass
Inspection date
Reported outcome
Pass
Inspection type
Canvass
Recorded citations
3
Source risk category
Risk 1 (High)
Inspection ID
1527816
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
This visit predates Chicago’s July 1, 2018 inspection procedure change.
Recorded violations
33
FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS - Comments: STUDENTS WATER FOUNTAINS NOT CLEAN THROUGHOUT THE SCHOOL,MOBILE UNITS,DEBRIS NOTED, INSTRUCTED TO CLEAN AND MAINTAIN.
35
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS - Comments: REMOVE DUSTS ACCUMULATIONS ON VENTILATION COVERS IN STUDENTS TOILET ROOMS LOCATED IN MOBILE UNITS. MISSING CEILING TILE IN THE PRE-K CLASSROOM#118.INSTRUCTED TO PROVIDE AND MAINTAIN.
41
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED - Comments: CLEAN AND ORGANIZE STORAGE CLOSETS IN PRE-K CLASSROOM#120,ELEVATE STORED ARTICLES AT LEAST 6" OFF THE FLOOR/WALL FOR EASIER CLEANING AND MAINTAIN.
CanvassPass
Inspection date
Reported outcome
Pass
Inspection type
Canvass
Recorded citations
0
Source risk category
Risk 1 (High)
Inspection ID
1434989
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
This visit predates Chicago’s July 1, 2018 inspection procedure change.
The source lists no violation citations for this inspection.
CanvassPass
Inspection date
Reported outcome
Pass
Inspection type
Canvass
Recorded citations
2
Source risk category
Risk 1 (High)
Inspection ID
1188612
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
This visit predates Chicago’s July 1, 2018 inspection procedure change.
Recorded violations
32
FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED - Comments: CAULKING AROUND THE WASHBOWL SINKS WORN OUT IN THE FOLLOWING AREAS: IN GIRLS WASHROOM 3RD FLOOR,BOYS WASHROOM 3RD FLOOR, GIRLS WASHROOM 2ND FLOOR,BOYS WASHROOM 2ND FLOOR, AND FIRST FLOOR BOYS WASHROOM. INSTRUCTED TO RE CAULK AND MAINTAIN. INSTRUCTED TO INSTALL A SPLASH GUARD BETWEEN THE METAL DRAIN BOARD OF THE 3 COMPARTMENT SINK AND THE EXPOSED HAND SINK RUSTY LID OF THE GREASE TRAP BOX UNDER THE 3 COMPARTMENT SINK. MUST REMOVE THE RUST AND MAINTAIN.
35
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS - Comments: VENT IN BOTH WASHROOMS IN THE MOBILE SCHOOL OUTSIDE WITH DUST BUILD-UP. MUST CLEAN IN DETAIL AND MAINTAIN. GIRLS WASHROOM CEILING ON THE 3RD FLOOR NOT MAINTAINED WITH DRIED TISSUE PAPERS ALL OVER THE CEILING,VENT COVER IN THE WOMENS WASHROOM 3RD FLOOR WITH DUST BUILD UP. MUST CLEAN IN DETAIL AND MAINTAIN.
CanvassPass
Inspection date
Reported outcome
Pass
Inspection type
Canvass
Recorded citations
2
Source risk category
Risk 1 (High)
Inspection ID
1098610
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
This visit predates Chicago’s July 1, 2018 inspection procedure change.
Recorded violations
33
FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS - Comments: INSTRUCTED TO CLEAN/SANITIZE; COOLER AND MICROWAVE OVENS INSIDE THE STAFF LOUNGE.
35
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS - Comments: INSTRUCTED TO REPAIR AND SEAL OPENINGS ON WALLS INSIDE 1ST FLOOR MOP CLOSET AND REMOVE PEELING PAINT INSIDE SAME CLOSET AND INSIDE 3RD FLOOR SOUTH AREA WASHROOM ON CEILING.
CanvassPass
Inspection date
Reported outcome
Pass
Inspection type
Canvass
Recorded citations
4
Source risk category
Risk 1 (High)
Inspection ID
522000
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
This visit predates Chicago’s July 1, 2018 inspection procedure change.
Recorded violations
34
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED - Comments: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST CLEAN FLOORS IN BOILER ROOM AND 2ND FLOOR MOP CLOSET.
35
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS - Comments: The walls and ceilings shall be in good repair and easily cleaned. MUST REPAIR BOILER ROOM WEST SIDE AREA DOOR.
38
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED - Comments: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR TOILET WATER TANK AT 2ND FLOOR STAFF WASHROOM AND PROVIDE ADEQUATE WATER PRESSURE FOR 2ND FLOOR DRINKING FOUNTAIN.
41
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED - Comments: MUST REMOVE UNNECESSARY ARTICLES FROM 2ND FLOOR STORAGE ROOM, CLEAN AND ORGANIZE TO PREVENT PEST HARBORAGE. ARTICLES MUST BE STORED OFF FLOORS, AWAY FROM WALLS.
CanvassPass
Inspection date
Reported outcome
Pass
Inspection type
Canvass
Recorded citations
4
Source risk category
Risk 1 (High)
Inspection ID
521407
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
This visit predates Chicago’s July 1, 2018 inspection procedure change.
Recorded violations
34
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED - Comments: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST CLEAN FLOORS INSIDE MOP CLOSETS AND STORAGE ROOMS.
35
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS - Comments: The walls and ceilings shall be in good repair and easily cleaned. MUST SEAL OPENING ON BOTTOM OF WALL INSIDE 1ST FLOOR MOP CLOSET TO PREVENT PEST ENTRY.
38
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED - Comments: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR HAND SINKS FAUCETS INSIDE 1ST FLOOR BOY WASHROOM AND 3RD FLOOR GIRLS WASHROOM. ALSO SEVERAL LEAKING PIPES IN BASEMENT.
41
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED - Comments: INSTRUCTED TO STORED ARTICLES OFF FLOORS, AWAY FROM WALLS TO PREVENT PEST HARBORAGE INSIDE SOME STORAGE ROOMS AND BOILER ROOM, AND REMOVE UNNECESSARY ARTICLES SAME AREAS.
CanvassPass
Inspection date
Reported outcome
Pass
Inspection type
Canvass
Recorded citations
2
Source risk category
Risk 1 (High)
Inspection ID
233323
Location recorded for this inspection · GROVER CLEVELAND ELEMENTARY SCHOOL · 3121 W Byron ST
This visit predates Chicago’s July 1, 2018 inspection procedure change.
Recorded violations
32
FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED - Comments: All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair.OBSERVED WALK IN FREEZER DOOR HARD TO OPEN INSTRUCTED TO REPAIR.
36
LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED - Comments: OBSERVED LIGHT OUT FRONT HALLWAY GOING TO LUNCHROOM INSTRUCTED TO REPLACE.
Local context · Chicago
How results compare in ZIP 60618
496 of 616 establishments with a Pass, Pass with Conditions or Fail outcome since July 1, 2018 have a Pass outcome.